Surge arrester & EMC/EMI filter PI-k16
(cu TVA) Add to cart Product is not available in stoc. Contact us! Warranty: 24 months Producator: HAKEL - TRADE s.r.o.
PI-k16 is intended to protect against overvoltages and high frequency signals for rack mounted data center and technical rooms equipment. It is connected in secondary power supply boards on each equipment or rack monophase (common or isolated neutral) power supply circuit.
Type PI-k16 |
|||
Nominal voltage |
UN |
230 |
V |
Max. continuous operating voltage |
UC |
275 |
V |
Nominal current |
IN |
16 |
A |
Nominal discharge current In (8/20) (L/N,L/PE) |
In |
3 |
kA |
Nominal discharge current In (8/20) (N/PE) |
In |
5 |
kA |
Combined impulse UOC (L/N, L/PE) |
UOC |
6 |
kV |
Combined impulse UOC (N/PE) |
UOC |
10 |
kV |
Voltage protection level at UOC (L/N) |
UP |
< 850 |
V |
Voltage protection level at UOC (L/PE) |
UP |
< 1,5 |
kV |
Voltage protection level at UOC (N/PE) |
UP |
< 0,5 |
kV |
Asymmetrical attenuation of filter at 4 MHz |
> 80 |
dB |
|
Asymmetrical filter attenuation in the band 0,15 - 30 MHz |
> 40 |
dB |
|
Article number |
30004 |
PI-k and PD*DS are a single-phase surge arresters type 3 with a high frequency filter according to EN 61643-11. They are produced for nominal current within the range of 8, 16, 25, 32, 50, 80, 120 and 150 A for application use in TNS systems. The types PI-k8, 16, 25, 32 A and PD*DS are constructed for mounting on DIN rail 35mm, The types PI-k50, 63, 80, 120 and 150A are produced in basic versions for mounting straight onto the construction of switchboard by four screws M4. PI-k and PD*DS are designed for protection of single-phase electronic appliances in LV, supply systems against impulse surge and high-frequency disturbance. This complex range is produced for nominal voltage within the range of 6, 12, 24, 48, 60, 80, 110,120,130,160 and 230 V (AC/DC).
The types PI-k8, 16, 25 and 32 are fitted with a green LED diode signalizing the right functioning, types PI-k16 DS, PI-k25 DS and PD*DS indicate the failure by target disconnection of mechanical thermal fuses.
Function of remote monitor terminals
When PI-k is operating correctly, the switching contact for remote monitoring is connected. Once the thermal fuse reacts to varistor overheating, the switching contact for remote monitoring will disconnect.
electric strength against surround circuits |
3750 Vrms |
electric strength against network circuits |
3750 Vrms |
insulation resistance |
2 x 107 Ω |
max. switching current |
~ 3 A |
max. switching voltage |
~ 250 V |
Details could be found in the Producer catalogue.